DataSheet8.cn


PDF ( 数据手册 , 数据表 ) DCS800

零件编号 DCS800
描述 DC Drive Technical catalogue
制造商 ABB
LOGO ABB LOGO 


1 Page

No Preview Available !

DCS800 数据手册, 描述, 功能
ABB DCS800 DC Drive
DCS800 20 A to 5200 A
Technical catalogue
PRODUCTS







DCS800 pdf, 数据表
Environmental Conditions
System connection
Environmental limit values
Voltage, 3-phase:
230 to 1000 V acc. to IEC 60038
Permissible cooling air temperat.
Voltage deviation:
±10% continuous; ±15% short-time *
- at converter module air inlet:
0 to +55°C
Rated frequency:
50 Hz or 60 Hz
with rated DC current:
0 to +40°C
Static frequency deviation: 50 Hz ±2 %; 60 Hz ±2 %
w. different DC current
+30 to +55°C
Dynamic: frequency range: 50 Hz: ±5 Hz; 60 Hz: ± 5 Hz
- Options:
0 to +40°C
df/dt: 17 % / s
Relative humidity (at 5...+40°C):
5 to 95%, no condensation
* = 0.5 to 30 cycles.
Relative humidity (at 0...+5°C):
5 to 50%, no condensation
Please note: Special consideration must be taken for voltage deviation in regenera-
tive mode.
Degree of protection
Converter Module and
options (line chokes, fuse
holder, field supply unit, etc.): IP 00
Enclosed converters:
Paint finish
Converter module:
IP 20/21/31/41
RAL 9002
Change of the ambient temp.:
Storage temperature:
Transport temperature:
Pollution degree (IEC 60664-1, IEC
60439-1):
Site elevation
<1000 m above M.S.L.:
>1000 m above M.S.L.:
< 0.5°C / minute
-40 to +55°C
-40 to +70°C
2
100%, without current reduction
with current reduction
Enclosed converter:
Sound pressure level
light grey RAL 7035
North American Standards
In North America the system components fulfil the requirements of the
table below.
Size Sound pressure level L (1 m distance)
P
as module
enclosed conv.
D1 55 dBA
?? dBA
D2 55 dBA
?? dBA
D3 60 dBA
?? dBA
D4 66...70 dBA,
depending on fan
77 dBA
D5 73 dBA
78 dBA
D6 75 dBA
73 dBA
D7 82 dBA
80 dBA
Vibration
as module
0.5 g, 5...55 Hz
1 mm, 2...9 Hz
0.3 g, 9...200 Hz
Rated supply
voltage
to 600 V
Standards
Converter module
Enclosed converter
UL 508 C
Power Conversion Equipment
CSA C 22.2 No. 14-95
Industrial Control
Equipment,Industrial Products
Available for converter modules
including field exciter units.
Types with UL mark:
• see UL Listingwww.ul.com /
certificate no. E196914
• or on request
UL/CSA types: on
request
>600 V to
1000 V
EN / IEC xxxxx see table above. EN / IEC types: on
Available for converter mod-
request (for details
ulesincluding field exciter units. see table above)
Regulatory Compliance
The converter module and enclosed converter components are designed for use in industrial environments. In EEA countries, the components fulfil the
requirements of the EU directives, see table below.
European Union Directive
Manufacturer‘s Assurance
Harmonized Standards
Converter module
Enclosed converter
Machinery Directive
98/37/EEC
93/68/EEC
Declaration of Incorporation
EN 60204-1
[IEC 60204-1]
EN 60204-1
[IEC 60204-1]
Low Voltage Directive
73/23/EEC
93/68/EEC
Declaration of Conformity
EN 60146-1-1
[IEC 60146-1-1]
EN 61800-5-1
(EN 50178 [IEC --])
see additional
IEC 60664
EN 60204-1
[IEC 60204-1]
EN 61800-5-1
EN 60439-1
[IEC 60439-1]
EMC Directive
89/336/EEC
93/68/EEC
Declaration of Conformity
(Provided that all installation instructions concern-
ing cable selection, cabling and EMC filters or
dedicated transformer are followed.)
EN 61800-3
[IEC 61800-3]
in accordance with
3ADW 000 032
EN 61800-3
[IEC 61800-3]
in accordance with 3ADW
000 032/3ADW 000 091
8 3ADW000192R0301 DCS800 Technical catalogue e c







DCS800 equivalent, schematic
External Field Supply
General data
Field converter types
• Currents from 0.3 to 520 A
• Minimum field current monitor
• Integrated external field power converter or completely
separate switchgear cubicle
• single-phase or 3-phase model
• Controlled by serial communication via DSL board
All field converters are controlled by the armature converter
via a serial interface (SDCS-DSL Board). This interface serves
to parameterize, control and diagnose the field converter
and thus provides an option for exact control.
We recommend integrating an autotransformer in the field
power converter's supply circuit to adjust the AC input volt-
age to the field voltage and for reducing the voltage ripple
in the field circuit for single-phase operation.
DCF803-0035
• Half-controlled thyristor/diode bridge (1-Q)
• Three-phase or single-phase operation
• Microprocessor control, with the electronic
system being supplied by the armature-circuit
converter (24 V).
• Construction and components have been
designed for an insulation voltage of 600 V
AC.
• Fast-response excitation is possible with an appropriate
voltage reserve; de-excitation takes place by field time
constant.
• Output voltage UA (single-phase operation):
U A UV *⎜⎝⎛1001%00+%TOL⎟⎠⎞ *0.9
TOL = tolerance of line voltage in %
UV = Line voltage
• Recommendation (single-phase operation):
Field voltage 0.6 to 0.8 * UV
• Output voltage UA (three-phase operation):
U A UV *⎜⎝⎛1001%00+%TOL⎠⎞⎟ *1.3 5
Table of field converter units
Unit type
DCF803-0035
Output
current I
DC
0.3...35 A
DCF803-0050
0.3...50 A
DCF804-0050
0.3...50 A
DCS800-S0x-xxxx-05 see table
on page 7
Note:
TOL = tolerance of line voltage in %
UV = Line voltage
Calculation valid also for FEX425 internal
AC field supply
voltage
110V -15%...500V/1-ph +10%
single-phase or three-phase
110V -15%...500V/1-ph +10%
110V -15%...500V/1-ph +10%
200V...500V/3-ph
auxiliary
supply voltage
24 V DC
200 mA
115 or 230 V
Remarks
external fuse
for 3-phase operation use ND01, ND02
for 1-phase operation use ND30 16A
if necessary via matching autotransformer;
fuse external; Dimensions HxWxD:
370x125x342 [mm]
additional hardware components (DCF
506)
Current reduction see also Environmental conditions in Hardware manual
16 3ADW000192R0301 DCS800 Technical catalogue e c










页数 28 页
下载[ DCS800.PDF 数据手册 ]


分享链接

Link :

推荐数据表

零件编号描述制造商
DCS800Drives Quick GuideABB
ABB
DCS800DC Drive Technical catalogueABB
ABB
DCS800DC module Firmware ManualABB
ABB
DCS800Drives Hardware ManualABB
ABB

零件编号描述制造商
STK15C88256-Kbit (32 K x 8) PowerStore nvSRAMCypress Semiconductor
Cypress Semiconductor
NJM4556DUAL HIGH CURRENT OPERATIONAL AMPLIFIERNew Japan Radio
New Japan Radio
EL1118-G5 PIN LONG CREEPAGE SOP PHOTOTRANSISTOR PHOTOCOUPLEREverlight
Everlight


DataSheet8.cn    |   2020   |  联系我们   |   搜索  |  Simemap