Temperature Controllers
E5CSZ
Easy Setting Using DIP Switch and Simple
Functions in DIN 48 × 48 mm-size
Temperature Controllers
• Easy setting using DIP and rotary switches.
• Models with two alarms added to Series, ideal for temperature
alarm applications.
• Clearly visible digital display with character height of 13.5 mm.
www.DataSheetM4Uo.dceomls available with black or white cases.
• RoHS compliant (Scheduled for January 2006).
Model Number Structure
Model Number Legend
Models with Terminal Blocks
E5CSZ-@@@@-@
1234 5
1. Output type
R: Relay
Q: Voltage for driving SSR
2. Number of alarms
Blank: No alarm
1: 1 alarm
3. Input type
T: Thermocouple/platinum resistance
thermometer (multi-input)
4. Power supply voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
5. Case color
Blank: Light gray
B: Black
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information when ordering.
Example
Relay control output, one alarm output, multi-input, light gray: E5CSZ-R1T.
Temperature Controllers E5CSZ
1







E5CSZ pdf, 数据表
2. Operation Settings
ON
Use the control mode switches (
) to change the
123456
control mode. (All switches are OFF for the default settings.)
ON
123456
Function selection
123456
ON/OFF PID control
PID ON/OFF control
ON
OFF
Control 2 s
period 20 s
www.DataDShireeectt4/U.coDmirect operation
reverse (cooling)
opera-
tion
Reverse operation
(heating)
ON
OFF
ON
OFF
Input Enabled
shift
display
Disabled
ON
OFF
Tempera-
ture
Sensor
selection
Multi-input
(thermo-
couple/
platinum
resistance
thermome-
ter)
Platinum
resis-
tance
thermom-
eter
input
Thermo-
couple
input
ON
OFF
Temper- °F
ature
unit
°C
ON
OFF
3. Alarm Modes
Select the number of the alarm mode switch 9 0 1 when changing
the alarm mode. (The default is 2).
Set
value
Alarm type
Alarm output operation
0, 9 Alarm function OFF
OFF
Upper- and lower-
1 limit
Upper-limit
2
Lower-limit
3
Upper- and lower-
4 limit range
Upper- and lower-
5
limit with standby
sequence (See note
2.)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
XX
SP
X
SP
X
SP
XX
SP
XX
SP
Upper-limit with
6 standby sequence
(See note 2.)
ON
OFF
X
SP
Lower-limit with
7 standby sequence
(See note 2.)
ON
OFF
X
SP
Absolute-value
8 upper-limit
ON
OFF
Y
0
Note: 1. No alarm. The alarm value (alarm operation display) will not
be displayed when the setting is 0 or 9 even if the selection
key is pressed.
Alarm Setting Range
X: 0 to FS (full scale); Y: Within temperature range
The value of X is the deviation setting for the SP (set point).
2. Standby Sequence Function (The standby sequence
operates when the power is turned ON.)
Rising Temperature
Dropping Temperature
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm ON
output OFF
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm ON
output OFF
Note: Turn OFF the power before changing the DIP switch settings on the E5CSZ. Each of the switch settings will be enabled after the power is
turned ON.
For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 6.
8 Temperature Controllers E5CSZ







E5CSZ equivalent, schematic
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Controller
E5CSZ
48 × 48
6
84
78
Panel Cutout Dimensions
45+00.6
L
z
www.DataSheet4U.com
E5CSZ
44.8×44.8
45+00.6
60 min.
Note: Terminals cannot be removed.
45+00.6
L = (48 × N2.5)+01
Mounting side-by-side
(group mounting of N Controllers)
E5CSZ + Adapter for Flush Mounting
(Provided)
Adapter for flush mounting
Panel Y92F-30 Adapter for flush mounting
58
E5CSZ
z Tightening
48 screws
7.5 76.5
Note: 1. The recommended panel thickness is 1 to 4 mm.
2. Group mounting is possible in one direction only.
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is available for the
following applications.
To protect the set from dust and dirt.
To prevent the panel from being accidentally touched causing
displacement of set values.
To provide effective protection against water droplets.
Terminal Cover
E53-COV10
48
48.8
°C
92A-48B
z
22
9.1
16 Temperature Controllers E5CSZ










页数 20 页
下载[ E5CSZ.PDF 数据手册 ]


分享链接

Link :

推荐数据表

零件编号描述制造商
E5CS-XTemperature ControllerOmron
Omron
E5CSZTemperature ControllersOmron
Omron

零件编号描述制造商
STK15C88256-Kbit (32 K x 8) PowerStore nvSRAMCypress Semiconductor
Cypress Semiconductor
NJM4556DUAL HIGH CURRENT OPERATIONAL AMPLIFIERNew Japan Radio
New Japan Radio
EL1118-G5 PIN LONG CREEPAGE SOP PHOTOTRANSISTOR PHOTOCOUPLEREverlight
Everlight


DataSheet8.cn    |   2020   |  联系我们   |   搜索  |  Simemap